Answer Posted / murugan
Large transformers for indoor use must either be of the dry type, that is, containing no liquid, or use a less-flammable liquid.
Well into the 1970s, polychlorinated biphenyls (PCB)s were often used as a dielectric fluid since they are not flammable. They are toxic, and under incomplete combustion, can form highly toxic products such as furan. Starting in the early 1970s, concerns about the toxicity of PCBs have led to their banning in many countries.
Today, non-toxic, stable silicon-based or fluorinated hydrocarbons are used, where the added expense of a fire-resistant liquid offsets additional building cost for a transformer vault. Combustion-resistant vegetable oil-based dielectric coolants and synthetic pentaerythritol tetra fatty acid (C7, C8) esters are also becoming increasingly common as alternatives to naphthenic mineral oil. Esters are non-toxic to aquatic life, readily biodegradable, and have a lower volatility and a higher flash points than mineral oil.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
can the measured percentage error during calibration of single phase energy meter be negative?
State thevenin’s theorem?
how to revers the direction of single phase motor
What is the source of dependent source ?
Battery is a voltage source? give one example of current source and why?
Explain marx circuit.
what is the Connected Load (kW) or Contract Demand (kVA)of mahindra nasik plant??
THERMAL CAPACITANCE IS MEASURED IN..................................................
how to increase senstivity of ct
What is the polarization index value ? (Pi value)and simple definition of polarization index ?
Explain about Leakage Test.
what is solkor relay and which condition it will act?
hi if anybody got model questions for cpcl Grade'A' electrical engineer position.send it to my mail please krishkumar22@gmail.com
given data are load current & power factor cable core size? plz any one update the calculation formula
WHAT IS MEANT BY DERATING OF THYRISTOR?