how to caluculate APFC panel rating, my running Load is
1320KW, Present P.F 0.76 to 0.8 we need 0.98 p.f
Answer Posted / deniram anandrao nikhare
KVAR Required = Operating KW x [Tan (A1) - Tan (A2)]
Where A1 = Inverse Cosine of present power factor
= Cos-1(0.78)
= 38.739
A2 = inverse Cosine of desired power factor
= Cos-1(0.98)
= 11.478
Tan(A1)=Tan(38.739)=0.8022
Tan(A1)=Tan(11.478)=0.2030
Hence,
KVAR Required=1320 x (0.8022-0.2030)
SO KVAR NEEDED TO ATTACHED=790 kVAR
| Is This Answer Correct ? | 38 Yes | 4 No |
Post New Answer View All Answers
What is the purpose of gravity tank in the stern tube
hello i have a problem !!!! i am studying gait analysis"human walking; and i had only single camera"sony 25 frames/s" and 2 separated force plates, and there is no synchronization between the camera and the force plates!. i wrote a matlab program to calculate joints moment(sagital) using inverse dynamics methode. and there is a problem with the output data!! can you help me.
How pipe flanges are electrically insulated?
How will you classify sliding contact?
what is the use of CW(Circulating water ,clarified water,cooling water),auxiliary cooling water(ACW),auxiliary raw cooling water(ARCW)in thermal power plant.plzz explain the different characteristics of these types of water.
What are the causes if one cylinder in a diesel engine has a high temperature?
Contaminants of fuel oil
"What is fuel oil viscosity, specific gravity?"
What is the formula to calculate how to find the amperes in 1ton and how many btu
why we use kg/cm2 in pressure gauge not kg/m2
Explain knurling.
what are the points that should be kept in mind during forging design?
Why are open the ejector air vents.
I am Sunny..I have completed B.Tech(Mechanical).can i apply for Probationary Officer Post in Syndicate Bank 2010.Is that they hire engineers for PO Post?
Identify the parts of indicator diagram?