how to caluculate APFC panel rating, my running Load is
1320KW, Present P.F 0.76 to 0.8 we need 0.98 p.f
Answer Posted / deniram anandrao nikhare
KVAR Required = Operating KW x [Tan (A1) - Tan (A2)]
Where A1 = Inverse Cosine of present power factor
= Cos-1(0.78)
= 38.739
A2 = inverse Cosine of desired power factor
= Cos-1(0.98)
= 11.478
Tan(A1)=Tan(38.739)=0.8022
Tan(A1)=Tan(11.478)=0.2030
Hence,
KVAR Required=1320 x (0.8022-0.2030)
SO KVAR NEEDED TO ATTACHED=790 kVAR
| Is This Answer Correct ? | 38 Yes | 4 No |
Post New Answer View All Answers
what are the different types of screws?
Why consumption of lubricating oil is more in two-stroke cycle petrol engine than four-stroke cycle petrol engine ?
Under what circumstances would there be an increase in pressure in a diver¬gent nozzle ?
Enumerate the cause of pumps low delivery of water
If you are scientist to b e and you wish to develop a self-generating power appliances, what would b e the ranking of importance to apply your concept of creating energy using alternator: 1. Washing Machine 2. Motor Water Pump 3. Electric Fan 4. Electric Stove 5. Flat Iron – Which one will b e your foremost and the least at the rank of 1 to 5? Why is that so? Defend your answer.
What do you understand by the concept of a 6 stroke engine?
What do you mean by the term thread size?
Why do you want to leave your last job?
why we cant measure absolute entropy directly,but the change we can?
What is the remedy if due exchanging, valve broke out during engine running operation?
What causes turbocharger surging?
Discuss how to prepare the M/E in the standby condition
A fan is handling hot air at 285 degC with flow of 411635 m3/hr, power consumed is 1165kW and efficiency is 66%. what will happen to flow, power and efficiency of the fan if a water spray system is introduced to reduce the air temperature up to 200 degC? (also please refer any document regarding this)
can someone explain tolerances on bolts what the symbols mean
How much is 1 kn in kg?