we convert 66kv to 33 kv to 11kv to 440v. why can't we
directly convert 33kv to 440 ?
Answer Posted / k.prakashchandra
440 V supply is for domestic and small industries located at
various places.With 400 V, the lines may extended to max 1
KM considering voltage drop and line losses.33 KV/433V s/s
requires circuit breakers and larger area. Hence can not
erected inside towns along the roads or underground.It is
economical and easier to have 11 KV sub-transmission lines
and 11KV/ 440 V s/s for public utility.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
why the check zone and main zone are used for Busbar Protn. scheem?
how many single tension hardware are required on a double circuit transmission tower?
i am studying in final year can i allowed for 23rd UES of Indian army
What are the necessary components of the feedback control system?
what is power factor ? how we can calculate the low power factor and amount of capacitor for improve that low factor ?
How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer
is IS says that neutral should be brought to switch box. and this one is a recomended practice
What is real time power factor control panel(RTPFC)?
How to Calculate KA Rating of Main LT Panel
How many types of oil using in H/T & L/T Oil Circuit Breakers. need Explenation ?
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
How can we calculate the motor frame sizes?
A well system is when , no. of bus bar is less or more. Tell me the concept of it.
Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com
The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.