how to calculate knee point voltage of current transformer?
Answer Posted / arup
Knee point voltage, Vkn = (VA X ALF)/ In
VA= Burden =30 (Say)
ALF= Accu. Limit. Factor = 20 (Say)
In= Rated Secondar Current =5 amp (Say)
Then Vkn= 120 volts
If CT Ratio is 2000:5 then In=5
Class is 5P20 then ALF=20, P=Protection CT
| Is This Answer Correct ? | 37 Yes | 10 No |
Post New Answer View All Answers
how much UPS neutral erath leakage current.
We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks
what is the ckt diagram of a tubelight and is it the simplest ckt of electrical engineering and also the component?
What is the meaning of C1, C61, C91 cable
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
wat is the current produced in a 5000v megger? when the positive and negetive terminals are touched on our body get s shock?
plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in
describe the phenomena of vacuum interruption in C.B
What is the method to solve circuit using source transformation?
what do u understand about FACTS? how they are useful?
What is Load sharing of Transformer ?
what is Fault level? why it is calculated? how will u decide same for our plant?
What is the need for a controller?
How to dimensioning SDCCH, LAPD and CS7 signaling on GSM?
i am going to give the JSEB,RANCHI exam for power plant,so i need some samples of papers related to that,so please send me these papers by my mail id.