Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

for distribution line ratio of x/r
1.<0.1 2.>10 3.>1 4.<0.01

Answer Posted / shantanu mishra

x/r ratio is the ratio of reatance of the line and
resistance of the line. In distribution lines like 400 volt
three phase line, the resitance is far high than reactance
or we can say the reactance is negligible as compared to R.
Therefore x/r ratio of dist.line is less than 0.01. for
11kv line this may be less than 0.1.
THis ratio increases as we move towards high and Exta high
votage lines.

Is This Answer Correct ?    29 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.

2081


THERMAL CAPACITANCE IS MEASURED IN..................................................

2087


why the starting voltage drop in a cable needs to be limited?what is percentage of the voltage drop allowed during starting?

1759


What is the difference between indoor and outdoor transformer

5841


Mr. mohh sahid m not satisfied for ur answer to the que weather the size of transformer increases or decreases withchange in fr for more detail go to the answer given by me

2080


can anyone show me how the 3 phase power is supplied to socket outlets?

1963


For small size, high frequency coils, the most common core material is- a. )Air b. )Ferrite c.) Powdered ion d.) Steel

2925


Define relative stability.

996


what is the earth current,reverse power,electrical trip generator short circuit,low voltage, high voltage please discribe me

2060


Atwhat condition reverse power relay will act?

2206


Define steady state error.

1023


What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.

2257


can we synchronize star system generators with delta system transmission line ? and how ?

2769


What is the technical difference between On delay timer and a Star delta timer?

1552


What is EMC filter in VVVF Drive ?

2674