hi frienda We have 750kva cater pillet dg set we are fasing
one diffrent proublam in dg we are start dg set after one
mint applying load around 450a load but dg was run 3 Or 4
mints after 3 mints dg was shuding down automatic how to
face this proublam pls tel any budy
Answer Posted / pillay
Can you determine why it is shutting down. is it a standby
genset, only works when there is a power cut and it operates
on its own. if it is one, maybe something is wrong in the
normal power present sensing circuit. when the DG runs it is
seeing as though the normal power is back so it should shut
down. or may be the stop signal is coming from the engine
asking it to stop.signals like low oil pressure over
temperature,over speed,
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?
Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?
Why magnetic flux produces an induced current?? what is the detailed procedure ?? ans plz
how technical is calculated in 11kv line and lt line
bsec exam syllabus (mis)
What aturn on methods of scr?
what is ground fault in ACB?
List the power rating of any 5 important electrical appliances used in houses.
Pl.brief me any electrical major fault you have rectified.
What range of speed can you get with the field control method of speed control of d.c. Shunt motor?
Suppose a 3 phase, 2 pole, 440V induction motor is driving a flywheel of 600mm diameter, 150kg mass. By using v-belt and pulley, the speed is increased to 4500 RPM. What will be the effect on motor current?
what are the steps involved in generator load test?
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
Describe the test procedure to determine the vector group
How test for Ddo vector group test condition?