why middle phase should used for earth fault and other
phases used for over current in overcurrent and earth fault
relay?
Answer Posted / vishal ingle
Not necessary to use only the middle phase.
our Back up protection cosist of two overcurrent elements
and one earth fault element.
under normal condition vector (IR + IY + IB) = 0
in fact middle phase is not used for earth fault prot.
Earth fault relay is connected between the star point of
all three phases (after O/C Relay) and the earth. if any
unbalance occurs, the unbalance current will flow through
the e/f relay.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
How to resolve if Diesel generator stop while running ?
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
Explain the function and difference of Restricted earth fault, simple earth fault and sensitive earth fault with connection diagram.
What fomula is used to calculate: 1. rated frequency withstand voltage, and 2. rated lightning impulse withstand voltage.
Why we used 690V in ACS 800 drives.Why dont use standard voltage like 415v or 1.1Kv
what things to be considered when designing UPS
hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.
either water sensor or flow meter,how we observe the water level, f any other equipment are in market ?
What are dcs and plc?
Define average demand?
how to select rating of HT Panel
what is differnce btwen lll and lllg faults
Write down the design procedure of commutaj.
armature is that part in which current is induced since in dc motor we supply current to the conductor so why we call it armature?
sir i ve applied for hindustan petroleum and power grid india ltd..and the exams on feb 22.can you pls send model papers and tell how to prepare for those.i need to get into any of these for sure.....