why middle phase should used for earth fault and other
phases used for over current in overcurrent and earth fault
relay?
Answer Posted / vishal ingle
Not necessary to use only the middle phase.
our Back up protection cosist of two overcurrent elements
and one earth fault element.
under normal condition vector (IR + IY + IB) = 0
in fact middle phase is not used for earth fault prot.
Earth fault relay is connected between the star point of
all three phases (after O/C Relay) and the earth. if any
unbalance occurs, the unbalance current will flow through
the e/f relay.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
how to apply b license to c license in tneb
for 11KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV UG system what will be typical per KM "R" "L" "C" parameter.
A Question Like A Wire Is Wound Whose Resistance Is Some 132. 44647 Ohms. If A Voltage Of 30 mv, 296 Ma Current Is Applied To It What Is The Resistance.
where was current transformer protection units used and why??
If there is major % of Voltage harmonics in the system, how can it be control or reduced?
How to calculate the copper in HT motors if KW, RPM & Voltage is given
Let me know that how i calculate the alternator sub tranciant reactance and tranciant reactance.
what is the use of surge suppresser in 33 KV incoming panel. where it must be installed,inseries with incoming cable surge suppresser must be at incoming of the breaker are outgoing of the breaker
How to check the cable fault / hv test of transformer cable.
why ct ,cvt should be stored in a vertical position?
what are the advantage and dis-advantage of 3 phase 4 wire energy meter?
WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME
how to calculate transformer load?
What do you mean by pull of electromagnet?
What is reactive power and where it is used.