What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / n. vajiravel
in case of star-delta trafo
if you apply single phase supply on primary 1u-1n then the
voltage should be divided to 1v-1n(70%) and 1w-1n(30%).
this result shows the correct magnetic coupling between the
windings.
example:
apply single phase supply to 1u-1n----100%(230v approx)
measure voltage in 1v-1n and 1w-1n then you will get
70% of 230V in 1v-1n and 30% of 230V in 1w-1n approximately.
apply single phase supply to 1v-1n-----100%(230v approx)
measure voltage in 1u-1n and 1w-1n then you will get 50% in
each.
apply single phase voltage to 1w-1n-----100%9230v approx)
measure voltage in 1u-1n and 1v-1n then you will get 30% of
230v in 1u-1n and 70% in 1v-1n approximately.
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
what is lrs tank water resistance.
What is milivolt dop test in Busducts? What is its significance & procedure to do the test?
State any two nuclear power stations in India, with their generating capacity.
What will happen if a dc source is given to a tubelight. Will it work or wont it work....
Why to keep capacitor bank off while generator running.
hi every body i am master student in control engineering and my project is slip control in trains i assumed a Dc motore as traction motor but i don't have characteristics of this kind of motor that is used in train. i want from every body if he or she has the characteristics or information about Dc motor that is used in train give me those information or technical characteristics .
What are hrc fuses and where it is used?
What are the application of filter?
What shall be the secondary output voltage if the primary winding of a 220/6V, 50 Hz transformer is energized by an 110V, 60 Hz supply?
draw the full wave and half wave circuit of 3 phase system and inverter circuit used in upsĀ
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1
why the projects getting loss?
what is the necessity of under ground cables ??
When we need up only in o/p 440v, so why we use directly in 11kva in input?