What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / n. vajiravel
in case of star-delta trafo
if you apply single phase supply on primary 1u-1n then the
voltage should be divided to 1v-1n(70%) and 1w-1n(30%).
this result shows the correct magnetic coupling between the
windings.
example:
apply single phase supply to 1u-1n----100%(230v approx)
measure voltage in 1v-1n and 1w-1n then you will get
70% of 230V in 1v-1n and 30% of 230V in 1w-1n approximately.
apply single phase supply to 1v-1n-----100%(230v approx)
measure voltage in 1u-1n and 1w-1n then you will get 50% in
each.
apply single phase voltage to 1w-1n-----100%9230v approx)
measure voltage in 1u-1n and 1v-1n then you will get 30% of
230v in 1u-1n and 70% in 1v-1n approximately.
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
why the field winding in dc motor is not short circuited eventhough dc supply is applied across the winding
If the rated speed of a d.c. Shunt motor is1440 r.p.m, which method of speed control would you suggested to obtain a speed of 1500 r.p.m?
if the motor rated speed is 950rpm. how to change the above rated speed? is it possible?
while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends
Some times to change of DOR of a motor, interchange of R & B is not effected and RYB take same current, but interchange of R&Y is effected ie change the DOR. My doubt is what is the problem in motor and how it is happen.
how can we calculate the ampacity of the electrical wire/cable. and what are the factors must be considered. pls. elaborate.
WHAT IS SPEC OF CLEANROOM MOTOR AND LIGHT FITTINGS?
We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?
11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?
When we need up only in o/p 440v, so why we use directly in 11kva in input?
How we can calculate the Amps for the cable Ex:- For 1sqmm wire how many amps we can draw (calculation)
There are Two questions about Steam Turbine Generator... What is HRSG bypass of LP, HP used for in power generation? In particualar, in the event that fault of HP bypass, there would be STG TRIP in operation but none on the LP bypass fault...what's the reason ?
how can you calculate fault level ?
how to select overload-relay for perticular motor 1.for D.O.L. starter 2. for Star-delta starter ????
what is the maximum temperature rating of a thhn insulated conductor?