i want to ask that as everybody knows that in star
connection on star point is called neutral. my question is
that why on that poin called neutral. what is the reason
behind it. what is the logic behind it. i heared somewhere
that on this point all phases current become zero thats
why. if this answer is right then prove why on that point
is current become zero. if this answer is not right then
tell me the right answer. post ur answer here or on my mail
address. m.ikram786@yahoo.com
m.ikram555@gmail.com.
thanks.
Answer Posted / kamlesh dewangan
In the three phase system all three phase current vector
sum to zero only if the system is balance (ie balance three
phase system).
_ _ _ _
I= Ir+Iy+Ib
These can be easily proved by solving following equation:
_
Ir = Im*sin(@)
_
Iy = Im*sin(@+120) Since in balance system all
phases are 120 degree apart
_
Ib = Im*sin(@+240) Since in balance system all
phases are 120 degree apart
_ _ _ _
now calculate I= Ir+Iy+Ib, it will become zero.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Why derating factor os applied on Cables?
How to design inductive load for 3 phase 440v and maximum 5 amps for star or delta? Can we use a 15kW, 1450rpm motor for 15kW, 960rpm apllication?If yes.how......n.if thesame motor used what`s it`s sideeefect.
how to select battery for 15 KVA UPS with formula
What do you mean by transformation ratio of instrument transformer?
what is EIB lighting control system? what is the advantages of this system?
what is the working process of over & under voltage relay.
What is meant by derating factor?
How vfd saving power.
Why control of DC motor is simpler?
which is the best institute for PLC,SCADA,DCS in hyderabad
What is Auto Mains Failure Panel & Auto Synchronizing Panel
What is expention fastener (Fan)
what is meant by poly phase induction motor ? how its operating by single phase or three phase?
Why the unit sizes of hydro generating machines are not standardized as in case of thermal powerplants?
Is it possible to measure correct value of earth resistance & cable insulation ristance with out disconncting earth lead & both sides of cable ends? If not, any other method to measure ER & CIR with out disconneting from the system.