For load of 1 nos 3 TR Air Conditioners,6nos of 60 Watt
Tibe Lights, 2 nos 200 W Outdoor Lights,1 no Coffee
maker.All may work at the same timehow do I select DG Set
Rating ,pLease advise the calculations
Answer Posted / vachaspati sharma
your total load is :-
3TR Approx. 3000 watts
60wattx06Nos 360 watts
200Wattx02 Nos 400 watt
Cofee maker Approx 500 watt
total load 4260 watt
say aprrox 5000 watt / 1000watt
5 Kw load
KW= KVA x P.F ( if PF .8)
KVA = KW/.8
5/.8
KVA = 6 ans
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
ratings of lightning arrester
electromechanical relay type identification example : type=tjmh t-stants for j- m- h-
HOW WE KNOW IN PHYSICALLY THE CONTACT SURFACE OF A VACUUM INTERRUPTER IS GOOD OR GOING TO DAMAGE IN A VCB AFTER ABOVE 500 TIMES OPERATED.
How Diesel Generator start ?
what does a string of resistors in a series will do?
What do you mean by reach and reach the point of the relay?
What is effect of over voltage and under voltage on ACB
what are the differant std sizes of cable trenches?
What is Plank's Law?
how to find the resistance and gap volatage of the diode??
How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).
In EHV transmission line a neutral grounding reactor is often placed at neutral point of shunt reactors. What is the recommended protection for this neutral grounding reactor? Should I use a fast closing switch to bypass neutral grounding reactor when this protection operates?
Explain the construction of the conservator, operation and purpose, and draw the diagram of the conservator.
Fantio of tranformer
What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating