For load of 1 nos 3 TR Air Conditioners,6nos of 60 Watt
Tibe Lights, 2 nos 200 W Outdoor Lights,1 no Coffee
maker.All may work at the same timehow do I select DG Set
Rating ,pLease advise the calculations
Answer Posted / vachaspati sharma
your total load is :-
3TR Approx. 3000 watts
60wattx06Nos 360 watts
200Wattx02 Nos 400 watt
Cofee maker Approx 500 watt
total load 4260 watt
say aprrox 5000 watt / 1000watt
5 Kw load
KW= KVA x P.F ( if PF .8)
KVA = KW/.8
5/.8
KVA = 6 ans
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
Define early construction of human being
Could the power factor on electrical system can affect the registration of the kwhr meter or the CT/PT?
How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
what type of earthing do for dry fissure rock?
How to justify this statement ??? "Capacitors in series provide less capacitance but higher voltage breakdown rating for the combination"
What are the two segments of nyquist contour.
why EMF IS INDUCED IN A CONDUCTOR WHEN FLUX LINKING WITH IT CHANGES ACCORDING TO FARADAYS LAW.
Can I use distributon class/transmission class Lightning arresots for protecting the building? If not why please explain?
WHAT IS SPEC OF CLEANROOM MOTOR AND LIGHT FITTINGS?
Differentiate between induced emf and self inductance?
Why strting torqe high in inducation motor?
Is there any guideline say about display of earthing value near to earth pit
how do i commission a distribution transformer knowing all its ratings and transformation ratios?d
3phase motor can be used as a Prime mover for alternator.