sir
what is the minimum IR value of 11 KV alternator?

Answer Posted / md. m. u. noman

IN my traning preod i face this question.i have learn 2 mathod.
1st IR >= system voltage in M ohm +1 M ohm.
for example, 3.3kV motor IR= 3.3+1 =4.3M ohm....that means
greater or equel to 4.3M ohm..

2nd is IR >= (20*V)/(1000+2P)M ohm.(at 25 degree celcise)
where , V= rated voltage ofmotor;
p= power in kW......

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the difference between droop mode and ischnorous mode in thermal powerplant?

2263


what is the effect of un-synchronized power.

1654


how to find three phase complex power in per unit and MVA?

1745


how does high earth to neutral voltage affect electronic equipment?

1053


What are two contours of nichols chart?

714






What is the difference between a Root Locus plot and a Bode plot?

875


What is the two pole structure?

1507


How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?

750


What is meant by analogous system?

883


hi frds, i m electrical engineer.can i get cdr for electrical engineer if u have then send me on my mail id its jayesh_ee88@yahoo.com.please help me frds

1750


Why the standard of ambient teperature mentioned as 40 degree celcius in machines.

1539


what is capacitor voltage transformer?? how it is different from potential transformer?

1777


what is quality factor in series resonance circuit and calculate the factor of voltage magnification? how it happens?

1588


What is cut-off rate?

869


Draw the vector diagram and condition for the following: 1) Dyn1 2) Ynd0 3) YnYn0

3293