Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to calculate the current carrying capacity of
electrical cables

Answer Posted / abdul haseeb khattal

Well, First try to calculate the total load of the system.
For example total load is 1000KW. The current can be
calculated as P=1.732VICOS(PHI). Hence total current will
be 1732A by considering V=415volt, power factor=0.8.

Step2: To calculate the cable size

Vd = mV/L/A

where Vd= Allowable voltage drop which is normally 2.5
percentage to 4 percent.
L = Lenght of the cable from the source to feeder
A = Ampere rating

Let us consider L = 1000Meters
A = 1732A
Vd = 2.5 percentage of 415V as in U.A.E.
= 2.5*415/100 = 10.375

Use these value in the above formula

mV= Vd/L*A
= 10.375/1000*1732
= 0.005 volt

Refer to the cable catalogue in your region and find out
the current carrying capacity of the cable which will be
totally depend upon the atmospheric condition, in cold
place a smaller diameter of cable can carry larger current
and in hot areas the same size will carry lesser current.

In U.A.E. we are normally using 11x1c 630sqmm cable with
2500A incomer breaker. But cross check the voltage drop as
calculated above is within the limit of voltage drop of
these cables else you have to go to higher size of cable
untill the voltage drop met the design milli volt drop of
the cable.

Is This Answer Correct ?    16 Yes 12 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

my b-tech percentage is 50%. what answer will satisfy the hr ?

2110


how can i get the formula to find out the cable size if i know the load of main fuse protection.

1941


what is the difference b/w ATS and HTS?

2186


what is earth pit , how we can measured it, what earth rods reference

2619


how single phase preventer works ?

2537


what is mean by restructuring power system?

2070


Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..

2593


how to find the capacitance value of the motor while running??

1937


What is the effect on Power factor and capacitor when your company load is more than 70 % of welding transformer

1819


how to apply b license to c license in tneb

1824


some basic standard questions on transformer.

1808


What is the numerical quantity of sqcm?

2033


What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?

2147


What should be the Sandwitch type Al. bus bar capacity for 2 M.W.Gen. set, having continuous full load current- 3463 Amps,ambient temp.- 50 Deg. C., Required temp. raise-20 deg.C., it will run 24 hrs, 365 days on full load, required highly reliable.

2684


which type of stability limit is higher,steady state or transient? why?

1906