why do power factor in the three phase induction motor
increases with the load ???.
Answer Posted / sharan dilip
In the -ph systems the pf decreases as load Increases.
But In the induction motor it quite different.
At no load or light load the current drawn by induction
motor is is comparable with the magnitude of the magnetizing
current which lags much behind the applied voltage and hence
low pf @ low or no-loads.
While the load increases the current drawn by the induction
motor increases. As the secondary of i.m. is short
circuited.The current operates at a higher power factor.
| Is This Answer Correct ? | 8 Yes | 7 No |
Post New Answer View All Answers
Consider three heater bank connected in 3 phase star with neutral.Each heater bank connected in each phase.So each phase get 230 volts supply.my question is,during balance condition, current flow in neutral or Not
how we test a 3 phase motor on single phase supply....? HOW WE RUN A 3 PHASE MOTOR ON SNIGLE PHASE. supply for testing..? how we verify of a 3 phase motors 6 wire & name thame a1/a2/a3..b1/b2/b3 and c1/c2/c3 for connecting star delta starter ........i have only 1 phase supply ? help forum..........
Logic using 1 kV or 1,1 kV grade in house wiring Low voltage cable. Explain/suggest? some use 1kV and some prefer 1.1kV grade insulation low voltage cable why??
How LT megger works ?
Iin ESP why positive is grounded ? why not negative ?
what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network
How to calculate the efficiency of Turbo Generator(Alternator) in general....?
How can maintain our H.T. motors used in cement plant. please send me procedure.
what is the isolation transformer. what is the isolator?
why ten delta testing is carried out on power transformer
is it possible for different brand of H.V transformers to run or operate in parallel to each other? if so how much disturbance can this affact the H.V bus bar?
before transformer oil dielectric strenght tests are taken the oil should be allowed to settle to remove option 1 air bubbles 2 gasses 3 contamination 4 water
what is dry and wet frequency withstand voltage? why & where it is used??
why magnetising curve not start with zero voltage?
A 100KVA SINGLE PHASE TRANSFORMER 10000/200V,50HZ REQUIRES 300V AT HV SIDE TO CIRCULATE FULL LOAD CURRENT WITH LV SHORT CIRCUITED.THE INTAKE IS 1000W.THE % OF REGULATION ON FULL LOAD AT 0.8 PF LAGGING WILL BE HOW MUCH AND THE SECONDARY TERMINAL VOLTAGE ON 0.8 PF LEADING WILL BE