What is linearity of RTD over 0 to 200 degC?
Answer Posted / dr. v.s.v.mani
0.4% of FS. The Pt 100 has 100 ohms at 0 degC, 175.8 ohms
at 200 degC. However at 100 degC, resistance is not 137.9
ohms but 138.5 ohms, which is 0.6 ohms higher. [Now 0.6/
(175.8- 100)]*100% is 0.8%. However with respect to a best
fit straight line, the deviation from straight line is +/-
0.4% of FS.
| Is This Answer Correct ? | 22 Yes | 0 No |
Post New Answer View All Answers
what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .
which type of zones used for boiler? & why ?
flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty
Draw a group of instruments interlocked to a Pump & Motor?
what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.
What should be the main consideration while starting the Rotating compressor when we dont know the cut in and the cut off pressure setting of the pressure switch
How digital input and digital output 's are working in dcs
What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem?
Q- Control problem are mainly classified in _____ types. a-)4 b-)3 c-)6 d-)nono of these Few of them i know is 1- regulator type problem (eg- Air conditioner) 2- tracking problem (eg missile trcking problem) 3- sybernatics 4- optimal control problem
How it the difference between force balance system and dispalacement balance system?
I have energy meter for educational project having 0.5s class but my friend need 0.2s class meter , which one is good for that purpose and what is the actual difference of that two classes , need very easy example also.??
how to measure oxygen which methods are using?
I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?
why we use impulse line of flow transmitter at 45 deg. angle both side of orifice plate.
anybody having Qatar Petroleum questions for instrument Technician offshore ....please send me