What is the difference between CT for protection and Ct for
metering?
Answer Posted / john bosco
METERING CT:
these types CT are construction wise Different from
Protection CTs. Generally the Core material used will be
different and Core area will be very less compared to
protection Cts. since the application/Requirement of
metering CT is to provide Accurate current for measuremet
at normal loading condition also should saturate for
fault/abnormal condition to prevent Meters connected to
metering CTs from damages resulting from high secondary
currents on fault condition. because meters cannot
withstand for such amount secondary current.
Protection CT:
CT used for protection relays are required to provide
accurate secondary current to relay measurement for
satisfactory operation on faults.
so these CTs should not saturate on fault conditions.
| Is This Answer Correct ? | 26 Yes | 1 No |
Post New Answer View All Answers
pre arcing time of ehv breaker
What is the purpose of stand by earth fault protection for transformer ?
Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega
What is the principle of HIGH SPEED DIRECT DRIVE MOTOR ?
What is the function of the circuit breaker failure relay?
how is working bearing heater?
How can i calculate the Breaking capacity of molded case circuit breaker, is the breaking capacity of CB for Diesel generator shall be less than grid supply's breaker ?
Define Electrical Insulation and examples of Solid,Liquid and Gaseous insulating materials?
Can anyone tell the proper diagram of star delta starter????
what is the usage of microcontroller in the panel board?
why you don not show protection and type of isolation in key single line diagram?
Terminal blocks is used for segregate the connections... There is any principle for terminal block..?
What is an ac motor?
What is steady state response?
Power Factor Correction Panel (Manual & Automatic)