Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the function of anti-pumping in circuit breaker?

Answer Posted / mohamed elias

The anti-pumping relay is a device in circuit-breaker whose
function is to prevent multiple breaker closures. For
instance, if the operator gives the closing command to the
breaker by pressing the close button and the breaker
closes. However, a fault in the system causes the breaker
to trip. Since the close command is still in the pressed
condition, there is a chance of the breaker closing again
and being tripped by the relay multiple times. This can
damage the closing mechanism of the breaker. The anti-
pumping relay prevents this by ensuring that the breaker
closes only once for one close command from the control
panel.

Is This Answer Correct ?    14 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how does a submersible pump work..?

1823


5.WHICH TYPE WELDING PROCESSES USES NON CONSUMABLE ELECTRODE.........

2028


Please tell me the power flow from pmg to main rotor of an alternator (Including AVR unit)?

1987


what are the major & minor faults that occur in an inverter and in UPS ? And how to repair and resolve them ?

2284


Why can't we parallel the secondary circuits of two voltage transformers?

1438


use of choke in APFC panels

5693


1) Explain why we don't link the two earthing system ht and mv on a pole mounted transformer sub-station.

1740


Is it true online ups having bypass mode if it is true then why we called ups because it is interrupting power when goes in bypass mode

1948


What are the advantages and disadvantages of short-pitched winding?

1040


how cables go in and come out for distribution from the feeder pillar box?

2026


During FEED, you will have all the information with regards to cable. How will you calculate the MTO for MV and LV Cables? what are your considerations?

2420


why do we use spark detector inside the slip ring brush compartment 0ona slip ring induction motor?

2033


Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir

1847


why current is constant on d.c?

2033


mostly the questions were from machines... d.c. machines, transformer, synchronous and induction all theory paper........ few from power system... but the level of paper was easy.....

1903