why is negative range given to measure the steam drum level
Answer Posted / sreekanth
Because of the wetleg compensation. In the drum the high
pressure is at the lower tap and Low pressure is at the
Upper tap. The wetleg is connected to the Upper Tap and the
DP across the taps will be -ve if there is no drum level.
so the range of the transmitter will be -XXX to 0 mmwc.
| Is This Answer Correct ? | 31 Yes | 5 No |
Post New Answer View All Answers
How we connect a instrument with ground, Give brief explanation with help of diagram?
how to change measuring units from mmwc to cubm/h in rosemount air flow transmitter with hart communicator fluke 744
what does it mean an active front end in vfd plz explain it briefly
How do bending tubing provide better measurement than using tubing fittings such as elbows?
What are the key features of a Distributed Control System? describing the various layers (sensor through to business system interfaces) as well as the hardware, software and security aspects of the DCS.
Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram
What is the advantage of using locally fabricated hook ups over Pre fabricated hook ups in process instrumentation?
what is span value and zero ? and how set ?
Why do we have earthing cable in branch cable and shield in the same cable?
in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
How to calculate P,I&D value in PID controller ?
NPN transistor, SCR, Zener diode, LED, Varactor diode, Vortex meter, RTD, Resistor, Crystal
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?