Energy metering:
On the property I am renting, the supply voltage is 2 x 110
volts. These 2 x phases enter a energy meter which then
exit the meter to over head lines to my house.
Question 1. The meter is single phase 240 volts but is being
used as 2 x phase(2 x 110volt), is this acceptable? if not,
please give me the reasons.
The meter details are as follows:
60Hz 15amp Imax 100 amp Kd 3,6 Wh/R 1 fase 3 hilos
Model FX 231.
I think it was manufactured in Brasil
From this meter, the cables run along over head aluminum
conductors,I estimate the cross sectional area to be 25mm
diameter, but the neutral is only about 10mm square
diameter, which cover a distance of 170 meters and then
terminate with an underground cable of 65 meter length,
total length = 235 meters.
There must be a huge voltage drop over this length. This
line is protected with 2 x 200 amp aluminum fuses after the
meter, there is no main switch in the distribution board.
These 2 phases connect directly onto 2 busbars. Surely the
neutral should be the same size as the conductors if not more?
Question2. What are your thoughts about this installation,
should there be better protection, is the neutral too small?
During the night, the lights dim then brighten all the time,
this cannot be good for my electrical appliances.
In my home, I only have a small electric geyser and fridge,
my stove works off gas. But when i use other appliances
like the washing machine or microwave oven, the light dim.
The internal wiring of this house is done with solid hard
drawn copper wires and of course, they have to be under rated.
I am a retired electrician by trade, but not on the metering
and over head mains side, my experience is on the factory
maintenance side of things.
Your expertise on these matters will be greatly appreciated.
Please inform me how to rectify or make any improvements
Kind regards, my power bill is very expensive, so I need to
know how to bring it lower.
Kind regards,
Brian
Answer Posted / k.prakashchandra
Considering your load, only one meter is sufficient for
you.The other meter could be for another house or two houses
have been converted into one or it could be for power
circuit.How many electric bills are received?. In case of 1
phase installation ,neutral wire should be of the same size
of the phase.Any way, voltage drop is high even for 10 sq mm
neutral wire.It seems that either the distribution
transformer is far away or cables used for interior wiring
are not of correct size.Also check for loose joints.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
which of the following elements is not present in stainless steel
Does outdoor isolator loose connection cause short circuit current in that circuit? if yes then how ??
How to justify this statement ??? "Capacitors in series provide less capacitance but higher voltage breakdown rating for the combination"
what are the preventive maintanance actions taken for air circuit breaker? please answer me
CALCULATE THE TOTAL VOLTAGE DROP AND SELECT THE CABLE SIZE IN MM-SQARE FOR A PANEL-262KW AT 110 METER FROM THE SOURCE SUPPLY , SUPPLY VOLTAGE 240/415
Why Ac Systems Are Preferred Over Dc Systems?
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
how we can calculate the efficiency of a diesel generator ?
please give me solution to rectify the emi(electromagnetic interference)
How npn and pnp transistor works
which connection is safer series or parallel?usually which connection we prefer at home?
Q: How to calculate Transformer losses , tell us by Formula.
State Maximum Power Transfer theorem.
What are the classifications of oscillators?
IN 1000kva transformer where the oil and winding temperature sensors is connected