How to calculate the Airconditioner capacity for a standard
telecom BTS shelter?
Answer Posted / chandrashekar
Genarally 1 Ton capacity means---The cooling produced by
melting of 1 ton of ice in a day is.taken as unit of
refrigeration (in tons). Now unit of refrigeration used in
S.I. System is KW. 1 ton of refrigeration = mass of ice x
latent heat of ice / 24 hrs i.e
= 900 kg x 335 KJ/Kg ( one short ton = 900 kgs )
---------------------
24 x 3600 secs
= 3.4895 KJ/Sec Now we should convert KJ to KW i.e 1KJ=1KW
so 3.5 KJ / Sec = 3.5 KW
that is 1 ton of refrigeration = 3.5 KW
Always in telecom sheleters we shold take the load of BTS
For Ex: In shelter there are 4Nos of BTS,If each BTS is
consuming 20A the total Amps for 4BTS is 80A.
So The total Load of the BTS is P=VI i.e
P=230*80=18400Watts i.e 18.4KW Now each 1Ton =3.5KW we can
suggest for 5Ton of AC for 18.4 KW
| Is This Answer Correct ? | 3 Yes | 9 No |
Post New Answer View All Answers
1.what is the reason for transformer and lightning arrester blast in 33kv system
How to protect a Dosing pumps/any sensitive equipment (single phase) from surge protection inside a food factory.
IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.
In all analog voltmeters or ammeter showing some small size symbols. as well as a star and in star 2no. digit, resister symbol,and other. what is that's meaning ?
bus bar design conditions and sizing pls tell me quickly
how can i change the rotation of the AC single phase induction motor and show me by diagram
What is resistance reading of earth copper rod with grid and without grid?
what is the current density of copper & alluminium.
How does cost of generation from hydropower plant compare with other sources of electricity?
define hysteresis loss, eddy current loss and windage loss
does buccholz in a transformer use batteries
how calculate gd2 of ht motors
What if high voltage side circuit breaker of a ehv transformer instead of lvcb? Kindly elaborate.
What is a difference between indoor transformer and outdoor transformer of same rating
We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?