why capacitor bank is not used in generator power
Answer Posted / k.prakashchandra
When the generators(gen) are connected to grid or net work
,if all the gens are run at unity pf ,there will be drop in
voltage due to inductive load in the system as the current
increases.Then to maintain system stability, LDC requests
large generating stations to increase the voltage . This
will increase the KVAR and results in lower lagging pf in
the gens. That is why the gens are designed for 0.8/0.85
pf.The pf of gens can be kept at any value by varying
excitation or resetting in APF mode.As pf control is
required by generating stations,capacitor banks are not used
.Capacitor banks can be used in the system to reduce the
inductive load but not in the gen stations.
Is This Answer Correct ? | 18 Yes | 1 No |
Post New Answer View All Answers
describe the A.C. Generator Testing procedure
sent to a site and asked to explain how you would like a twenty seven flour building should be supplied with lighting and sockets plus a water boiler.
Can anyone tell the proper diagram of star delta starter????
when it is possible kvrah lead & fundamental kwh be equal in electonic trivector meters (3 ph)
what is magnetizing and demagnetizing current in generator and motor?
work of choke in florocent tube circuit ?
What is excitation in case of dc motor?
WHY IN AC DRIVES,INPUT PHASE CURRENT SHOW UNBALANCE?
why the rotor current becomes in steady state during high slip region? please verify with equations.
what is Insulation monitoring device. where it is used? (in switchgear room or control panel or in field equipment)
what happen when we add mentos in cold drink?& why?
HOW TO CHECK THE VECTOR GROUP OF A TRANSFORMER YD11?
Can anybody please refer the best and simple book for about Protection relays and in detail of all its protection ?
What are protections for dty type transformers
is it possible to test of bus bar in high rise building without completed full floor ?