Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is the difference between pneumatic and electro
pnematic positioner?

Answer Posted / mohammed abbas

The difference between pneumatic positioner and electro
pnematic is that.
Pneumatic positioner will get the control signal in the
form of pneumatic (air) from the controller that is (3 to
15 psig)as a input to the pneuamtic positioner and it will
compute and give the pnematic output to air operating
devices or final contol element.it is pneumatic to
pneumatic converter and works totally on pnematic air
only.it will work on the priciple of force balance
mechanism.
Electro pneumatic positioner will recive the control signal
in the form of electrical signal that is (4 - 20ma)and this
elcetrical siganl through positioner it is given to i/p
converter wihch is inbuilt within a positioner body and the
elcetrical sigal will induce magnetic energy aronud the
coil and it will move the fallper away or close from the
nozzle and the nozzle pneumatic back pressure will insrese
and decrese depending upon the eletrical signal .it will
convert electrical signal to pneumatic.it will work on the
priciple of faradays law of electromagnitism.

Is This Answer Correct ?    57 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Hi Friends i am going to write BARC written test by this month 20th (20-5-2008). So please if any body knows the details about this or having previous question papers pls mail me to kkumarei@gmail.com. For Suggestions give one message to 9962122264

2449


How it the difference between force balance system and dispalacement balance system?

2144


why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?

2260


what is KV and XV valve

1842


What is limitation of the ht.of the displacer of a level trol?

2459


what is temperature compensation?

5525


Which type of pressure can be measured by primary elements?

1088


1.what is controller proportional gain 2.what is the controller intergral action time. 3.A proportional plus derivative controller that has a proportional band of 20% and a derivative action time of 0.1 minutes. Construct the shape of the output waveform for the triangular input if the input rises and falls at the rate of 4 units per minute.

2731


What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)

2155


Explain bernoulli’s theorem.

1109


How to interfacing microcontroller with a DC motor

2110


can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.

2318


Explain why use mmwc unit?

1101


all types of liquid analyzer principle with drawing?

2012


How to Calibrate Level Troll in field

1458