Answer Posted / ripul gosh
Hi Varadharajan,
It can't be vice versa because vent hole is used for liquid flow in pipes. If any gas gets trap being lighter in density it will go towards upside of the orifice plate. For this reason vent hole is on the upper side.
Drain hole-which is located towards the lower side of the orifice plate used for gas flow in industrial pipes. It is obvious that any particle will higher in density than gas and will always try to be on the lower side of the pipe. So drain hole provision is made so that the trapped solid or liquid particle will easily go out of the orifice plate.
Both the holes are provided so that the trapped material can't cause any erroneous reading in the differential pressure measurement.
| Is This Answer Correct ? | 22 Yes | 0 No |
Post New Answer View All Answers
Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
what is interface level measurement.who can calibrate interface level measurement transmitter online
How to convert mmWc(mili meter water colam) to tph(ton per hour)?
How oil line flow measured?eplain about instruments used and working principle?
what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.
Whatis the reset ofset and control system in instrumentation
what are the different types of Protocols? & their applications.
What is 3 element control system
How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.
HOW TO SOLVE PROBLEM WITH ENRAF LEVEL TRANSMITTER 854 ATG THAT PASSWARD DO NOT Exist INTO TRANSMITTER TO ADJUST LEVEL WITH PORTABLE PET 847, WRITTEN WRONG PASSWORD , I AM SURE THAT DEFAULT PASSWARD (W2=ENRAF2) IS THIS TRANSMITTER NEED TO REPLACE SOFTWARE AND HOW?
-/5A. What is the meaning and limitations of this in energy meter constant. It is a 3 phase LT Energy Meter. If this Energy Meter is connected through a CT of ratio 200/5 Amps, then what is the multiplying constant and how its will be calculated.
Why boiler chimney area oxyden sensor fixing?
How to Calibrate Vortex Flow transmitter in field