we are operationing 3NOs 800 Kva generators by
singronyus.specialey evening time our panel trip. the panel
showing generator earth fault
Answer Posted / k.prakashchandra
Another probability. If there is any earth fault before the
GT primary bushings ,the gen may trip on SEFR if voltage
based( open delta) relay is used.Then you have to check
cable,termination glands and the stator winding for earth
fault either by meggering or better by applying rated voltage.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
How can we calculate ac current from the given DC current when AC voltage is given?
How to do stting of vl250 siemens MCCB
Dyn1 transformer vector group testing how to do
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
wat is the first thing dat is needed, 2 lay a cable in some area??
How to decide CT & PT ratings for a given transmission line carrying some rated voltage?
What is mean by Sensitive Earth fault & what are the effects
if we have 320KVA Genset kindly advice how much load we can put it.
What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer?
how to select the double earth conductor if 21A full load?
How earthing/grounding done in aeroplanes and ships.
when we gave dc supply to 220v dc motor its rpm is 1200. then we gave 180v. how many rpm of its motor. gave answer with calculation at my ID.... ravizak@ymail.com
Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?
how we can calculate chiller required ampear?