what is main difference between live tank and dead tank
current transformer?
Answer Posted / samiran bairagya
Following are the advantages of Live Tank over dead Tank :
a) The Primary conductor is short than (in live tank CT) than the Dead tank CT which gives better Rigidity and gives high short circuit current withstanding capability and reliability.
b) Primary winding is uniformly distributed around Core, Hence CT is truly low reactance type, which has inherent better transient performance.
c) Due to shorter length and the tank being live the major insulation is not over the high current carrying primary, which is the main source of heat (as in the case of Dead tank type design.) the insulation does not get heated up while dissipating the heat generated. This facilitates much superior thermal stability of insulation and longer life
Is This Answer Correct ? | 20 Yes | 8 No |
Post New Answer View All Answers
what is ratio of copper wire size and current ?
We are designer please help me calculate the size of 11kv cables from step up transformer to M.V panel, total load is 5 mega watt distance 900 feet (used aluminum type cables) please provided formula for calculate the cable with example.
What is “pu” in ee?
any idea abt REVERSE METERING concept.........?
What is magneto on a gas generator. how it functions. its out put is d.c or a.c. how it can be checked for correct functioning
How to megger test 11 kV cable and the acceptance IR value
Can any body tell gulf interview question for experienced electrical engineer ?
Anybody tell me about modbus hex address of l&t trivector meter er300p??I want to read voltage,current,kwh etc via rs485...If anybody have a manual then send on my mail..Brijeshmodi18@gmail.Com
in dc series motor if field wdg is shorted then
Explain about technical and non technical losses in distribution system?
how to calulate short circuit current for the following: 1.cable connecting 11KV of 22KV/11KV transformer to 11Kv of 11KV/415V transformer 2.what cable size should i use.
What will be the fault current of any system when its generation is 10% of BASE generation( FUll Load )?Will is 10% or the same as full base calculation?
Why do we mostly prefer to generate and distribute electricity in 3 phase and not in 4 phase or 5 phase?
What is the distance between body earthing and neutral earthing.?
What is the requirement of grounding the neutral of single phase generators on load? If the neutral is not grounded, what will be the effect?