I did oil BDV test of 1600 KVA trafo 20KV/400V as per IEC
156. Result is 1) 58 KV 2) 58 KV 3)40 KV 4) 50 KV 5) 58 KV
6) 18 KV. Avr is 47 KV. Can we say oil is still ok even in
the 6th test BDV is 18 KV ?

Answer Posted / k.prakashchandra

It is OK for voltages up to 170 KV.It appears that you did
not stir the oil properly during the last test.When in
doubt, it is always better to test another sample.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Metal covered multiconductor cables shall employ a marker tape located within the cable running for its complete length in lieu of cable surface marking. Is it true or false?

1742


Why does the rotor rotate?

1815


How 3 phase invertor works?

1502


What is the formula to calculate the no load current of a single & three phase induction motor

1773


Whether it is possible to measure energy at the input of rectifier transformer (12 pulse with very high odd harmonics)

1472






How the over load setting for HT Motors calculated-provided in Numerical Relay

1198


Why star delta starter is preferred with induction motor?

635


what is the differences between microprocessor and general purpose computer

1639


what is ramping rate of generator

1567


how test transfomer(3 phase75kva) by megger

1620


Write down the brushes of a de machine.

1428


how to size H.T & L.T Panel ?

1643


Explain RLC circuit?

738


A 3-PHASE TRANSFORMER IS USED TO STEP-DOWN THE VOLTAGE OF A 3-PHASE, 11KV FEEDER LINE. PER-PHASE TURNS RATIO IS 12.FOR A PRIMARY LINE CURRENT OF 20A, CALCULATE THE SECOUNDRY LINE VOLTAGE, LINE CURRENT AND OUTPUT KVA FOR FOLLOWING.A)STAR- DELTA.B)DELTA-DELTA.

2451


Electrical 'C' license full abbreviation , and full form

1335