Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I did oil BDV test of 1600 KVA trafo 20KV/400V as per IEC
156. Result is 1) 58 KV 2) 58 KV 3)40 KV 4) 50 KV 5) 58 KV
6) 18 KV. Avr is 47 KV. Can we say oil is still ok even in
the 6th test BDV is 18 KV ?

Answer Posted / k.prakashchandra

It is OK for voltages up to 170 KV.It appears that you did
not stir the oil properly during the last test.When in
doubt, it is always better to test another sample.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the actual calculation for transformer short circuit test?.

2475


Electronic circuit

1041


what are the disadvantages in GIS over AIS

2434


How to calculate LT XLPE CABLE for 11 kv / 433 v , 1000 kva oil type transformer system?

1929


i want to know about torque of slip ring induction motor

2140


orifice sizing how done, checking & selection

1969


all interview questions with answers of ntpc (2000-2009

2218


Do closed loop systems require manual input?

1170


how to apply b license to c license in tneb

1826


We have 5 Distribution sections with variable loads&We have 3 Gensets(500kva,380kva&250kva) our total load is between 400kva to 600kva. so how could we connect 3gensets.

1860


how to find Harmonics and types as per the equipemnts

1299


How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?

1925


Why do you have to use Protecion relay with the function MTB ( Mechanical Trip Button ) for electrical system.

2213


What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.

2425


Anyone who can recommend an equivalent to Envirotemp FR3 of Cooper?

1983