check list of maintenance of transformer?
Answer Posted / vinod
Maintenance :
1) Power Isolation of transformer with proper permit
2) Earthing of all hv/lv terminal after physical isolation.
3) Cleaning of transformer with lint free cotton.
4) Oil leakages checks for all joint
5) Silica gel re heating if reqd.
6) OLTC/OFTC local operation Check(calibration of motor
over load relay)
7) OLTC continuity check(by connecting analog meter across
across all the phase terminal and OLTC operation)
8) Alarm and trip circuit checking of OTI,WTI, MOLG, Mulsy
fire,Buchholtz of main and OLTC
9) BDV of main Oil and OLTC oil
10) PPM of oil
11) Tan delta of bushing, main Oil and OLTC oil
12) Magnetic balence
13) Ratio test in every tap
14) Winding resistance
15) Insulation resistance after LA disconnection
16) Secondary injection test of protection relays with CT &
PT test
17) Cooling Fan testing by OTI/WTI temprature (manully by
rotating the prob)
18) Other inter lock if any
Note: Normaly Annual maintenance cover most of the the
test, mainly 5 year test contain all the checks depends on
manufacture and customer check list.
| Is This Answer Correct ? | 48 Yes | 6 No |
Post New Answer View All Answers
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
what are inherent currents?
importance of reactive power management
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.
am commissioning the trafo without connecting the neutral therefore unbalance will occur what is the alternative solution for this?
what is thresold of perception
I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing
What is an 86-P or an 86-A trip
Dear sirs, pls check this 4-20ma to RS485 module datasheet,pls guve me some suggestions. http://www.szsunyuan.com/sy/pro_more.asp?Productid=539 Thanks. E-mail:yunianjiang99@gmail.com
Metal covered multiconductor cables shall employ a marker tape located within the cable running for its complete length in lieu of cable surface marking. Is it true or false?
Write down the name of 2 lady Bir Pratin of Bangladesh
What are the essential characteristics of signal flow graphs?
how to measure the transformer resistance values(dyn11)?and howmuch the minimum value?
what clearance required for 4.5 mva dry type transformer?
Draw the DOL starter and star delta starter drawing?