we are operationing 3NOs 800 Kva generators by
singronyus.specialey evening time our panel trip. the panel
showing generator earth fault

Answer Posted / k.prakashchandra

Which relay ? SEFR or back -up EFR ? Are the gens connected
to grid ? Whether all the gens trip simultaneously ?
Whenever there is a momentary heavy earth fault in the
outgoing feeder,all the gens trip on back-up EFR with
instantaneous trip indication,though the line does not
trip.So ,it is advised to disable instantaneous fault trip
i.e. high-set of the back-up EFR.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

If 22 KV HT line, Current transformer is 25/5 then how to calculate multiplying factor.

613


A 3 phase transformer's (Y-Y) Y and B phase is (Y and B connection not broken) broken from neutral and R and Nutral connection is ok, what will be the relay tripping and why

1484


what could be the RMS value and average value of a 4 phase sine wave?

1418


what is the affect of earth's magnetic field on the frequency used in aircraft???

1543


How to decide the size of the capacitor for a single phase induction motor say 2 HP ??

1646






why they were using TRIAC instead relay in some controllers and what is the advantages.

1518


What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?

1340


what is a vector protection in transformer

1522


How capacitor improves pf

1200


what is size of 3phase 4wire cable to be used for 11 ton ductable A.C and how to calculate cable size for different load

3592


1. Design a counter which counts 0, 4, 8, 2, 6, and repeats using: 1.a using JK flip flops 1.b using T flip flops 1.c using D flip flops

1506


What is the armature mmf in a D.C machine?

794


What happened when capacitor connect series in ac circuit?

968


diff.between servo motor and ac motor

1561


Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632

2247