we are operationing 3NOs 800 Kva generators by
singronyus.specialey evening time our panel trip. the panel
showing generator earth fault
Answer Posted / k.prakashchandra
Which relay ? SEFR or back -up EFR ? Are the gens connected
to grid ? Whether all the gens trip simultaneously ?
Whenever there is a momentary heavy earth fault in the
outgoing feeder,all the gens trip on back-up EFR with
instantaneous trip indication,though the line does not
trip.So ,it is advised to disable instantaneous fault trip
i.e. high-set of the back-up EFR.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir
What difference between ref protection and differential protection ?
How the PF control while running DG set with load
how to identify conection leads of an unknown electric motor
How to calulate Locked rotor amper(LRA) for compressor type motors?
give single line diagram of D.G distribution form alternator to main L.T panel?
what is servo motor & how does it work.
For electrical designers what are the standard should know? i want learn about this standards. how to get information/reference. anybody help in this regards please.
please anybody help me to find out the BHEL trainee Exam previous year questions papers . if u ve pls. send it to surekhared@gmail.com
define reflection method?
WHAT IS START TO INDUCTION MOTER IN STAR TO DELTA OF >5HP ?
For a 6.6kV Motor it is recommended to do megger test with 500 V d.c and not more than 5kV d.c but the Hi voltage withstand test should be performed by 12kV AC. Why the dc voltage test should be limited but AC voltage withstand test could be with such a high voltage?
How to find ampere on ht side for selection of cable size ???
What is the effect of interchanging core(made of steel) and winding(made of copper) material in case of transformer? Give proper explanation in regard to different losses in transformer.
Define pole pitch?