Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

we are operationing 3NOs 800 Kva generators by
singronyus.specialey evening time our panel trip. the panel
showing generator earth fault

Answer Posted / k.prakashchandra

Which relay ? SEFR or back -up EFR ? Are the gens connected
to grid ? Whether all the gens trip simultaneously ?
Whenever there is a momentary heavy earth fault in the
outgoing feeder,all the gens trip on back-up EFR with
instantaneous trip indication,though the line does not
trip.So ,it is advised to disable instantaneous fault trip
i.e. high-set of the back-up EFR.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is star delta starter? how it works? give its control and power diagram.

2135


what is vtg limit of earth and neutral at transformer side?

2080


what's producer of XLPE cable laying in undergroung

2187


why we use two slope(differential & restraining) in differential relay.but in busbar protection differential we are using only one slope?please explain

2329


Why need 3phase machine double earthing?

1829


What is the emf equation of a transformer?

1316


how to select energy meter? have any calculation?

3069


Why earthing is necessary for any equipment?

1780


what is meant by motor startup supervision & motor load jam protection ?

6076


What is the safety of UPS?

2108


A low wet bulb temperature indicates

1206


Why synchronous motor is used in power factor improvement,dc series in lift

1695


how to select correct size of power cable for inverter duty motor

1637


Which type of motor is used in trains, what is the rating of supply used explain working principal?

1332


Benifits of 3ph 4 wire metering over 3ph 3 wire

2519