Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

hi frienda We have 250kva cater pillet dg set we are fasing
one diffrent proublam in dg we are start dg set after one
mint applying load around 450a load but dg was run 3 Or 4
mints after 3 mints dg was shuding down automatic how to
face this proublam pls tel any budy

Answer Posted / abdulgafar

A full load current of 250KVA DG Set is approximatly 350A.
Most of the DG Sets are designed to catter approximatly 10%
over load For a period of one hour hence a 250KVA dg set
can catter 385A For a period of one hour. you have applied
more load then the DG Set can catter/ deliver hence your DG
Set is triping automatically after about 3 min. hope i have
answered your question.

AGM

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT IS THE PARTIAL DISCHARGE TEST?

2105


Pls explan the OLR setting in VCB at HT yard

2679


Why a tesa lamp is glow between two phase?

1990


why incomer bay is required before transformer bay if there are more than 1 nos. of transformer bay.

3070


Why the output of OP-AMP is always less than Vcc?

1903


What is the difference between Droop vs Isoch Control?

2427


What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr

1065


What is error of a measurement?

1205


How will you define capacitance?

1148


If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..

2481


how to choose cable size with respect to load? how to convert cable size in mm2 to sq.mm?

5973


why ahould you show client/engineer activities clearly on the project plan

2768


Please provided formula for calculate the cable size from step up transformer to M.V panel, run overhead aluminum cables, total load is 5mega watt, total length 900 feet.

1756


what ispositive, negative, zero sequence impedence?

2021


where solid grounding and where grounding through ngr done and why?

2565