I want to give Power supply to a house from the Feeder,
Total Load of the House is 128 KW, how to calculate cable
size for this load ?
Answer Posted / s. patel
the equation of Power:
P=VICos (phi)
for single phase:- if load is 128 kw for single phase
then...Iph=(p/vph Cos(phi)(assume:p.f=1)
= 128000/(240x1)
=533Amp so this need 400-500sq mm 1 core of copper ok...
and if 3 phase is there
then
p=1.73xVLxILxCOS(phi)
IL=128000/(1.73x415x1)
=178Amp
if it may p.f is down up to 0.85 then current rating will increase by 200 to 210 Amps
so we have to select the cable as per their current carrying capacity up to 210 amp for three phase connection.
So we have to select 95 sq mm x 3 core...ok
| Is This Answer Correct ? | 10 Yes | 1 No |
Post New Answer View All Answers
What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2)
Operation carried out in thermal power stations?
What is proportional controller?
Starting current of a 10 HP induction Motor is ______ time’s full load current.
Why star delta starter is preferred with induction motor?
I am going to appear RRB Sr. Section Engineer Exam, Electrical. Can you send me previous year questions of RRB Electrical engineer. specially Section Engineer questions. my email id is likerahulworld@gmail.com
What is the basic rule for block diagram reduction technique?
Please provided formula for calculate the cable size from step up transformer to M.V panel, run overhead aluminum cables, total load is 5mega watt, total length 900 feet.
Refernce currents are to be generated using refernce cueernts how can this be done
In both 600/1000 V cable and 450/750 V cable, we can supply 415 V. However for distribution, all utilities are using only 600/100 V instead of 450/750 V. What is the reason?
Define relative stability.
How harmonic block test are conducted on relays ( Siemens,Areva ect )power transformer using omicron kit?
What is the difference between amorphous core transformer and CRGO core transformer?.
difference between power surge and switching transient
A Generator is in running condition and Rotor earth fault alarm is coming.How to check on line(i.e in running condition) whether there is actual earth fault in rotor or not.