difference between dol and rdol startors?
Answer Posted / madhu
RDOL IS NOTHING BUT REVERSIBLE DIRECT ON LINE STARTER.
This kind of starter is required when the motor is required
to run in both forward as well as reverse directions
according to the application.
Power circuit: There is one more power contactor connected
across the power contactor in the power circuit with two of
the phases interchanged to achieve reversal of rotation. The
two contactors are mechanically interlocked to ensure that
both of them do not operate simultaneously. The shorting of
two different phases is avoided through this arrangement.
Control circuit: The control circuit obviously consists of
two start push buttons, one for ‘FORWARD START’ and another
for ‘REVERSE START’. Each of them controls the supply to the
respective contactor coils responsible for the supply to the
motor in forward and reverse modes. The stop command is
common for both modes since it is independent of type of
operation. The NC contact of forward contactor is connected
in series with reverse contactor coil and that of reverse
contactor is connected in series with forward contactor
coil. This is the electrical interlock, which ensures that
only one contactor will pick up at a time avoiding any
mal-operation and consequent damage to the feeder and
problems to the dependant processes.
•
Indication circuit: One more Red LED is required to indicate
the ‘Reverse ON’ mode.
One NO contact of the reverse contactor is connected in
series with it.
Is This Answer Correct ? | 26 Yes | 6 No |
Post New Answer View All Answers
What do you mean by pull of electromagnet?
What is the two pole structure?
Difference between RCCB, RCBO and ELMCB.
How you will determine the volume of oil in a particular Distribution transformer.
new 90kw motor installed so how I purchased cable ,fuse,etc please give me technic for cable selected why always capacitor delta connection
How do we calculate over and under frequency tolerance from generator data?
WHAT IS THE PARTIAL DISCHARGE TEST?
how to determine ct ratio in ht vcb?
I NEED RRB APTITUDE QUESTIONS AND MODEL PAPER,PLEASE SEND MY E-MAIL joo28_eee@yahoo.co.in
What is critical disruptive voltage?
Is potential difference materials property ..? if yes tnen how.. explain brifly.
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to reconfirm its base capacity.
wht is embedded systems? what is new inthis field?
Trafo ratio is 11kV/6.6kv,Vector group is YND11. What will be the effect if secondary is used for earthed system.
What are the factor to be consider for CT selection in 132kV substation?