How Much Capacity of Diesel Genset is suitable for
20 no.s of 1.5ton AC's & Why?(Load Calculation)
Answer Posted / vivek sri
A correction to my earlier answer(8)
In case we are to use a 3 phase generator then the total
current of 218.75 has to be equally shared between the 3
phases i.e. Iph=218.75/3=72.9 Amps.
So the genset rating would be again 52.5kVA(1.732*415*72.9).
But in actual as the number of AC's is 20;
18 Ac's get distributed equally (6 on each phase L-N) and
the balance 2 nos will be on one phase each.
So the max current will be 76.58 (18/3*10.94+10.94).
So the 3 phase genset rating would be 55kVA (1.732*415*76.58)
| Is This Answer Correct ? | 10 Yes | 2 No |
Post New Answer View All Answers
What is cable tray, its type, and its support?
Safety of on line ups
What is transient Phenomenon?
what is the Transformer Impedence?How can calculate?
what happend to DC shunt motor if its field winding insulation becomes slightly weak? will that motor can run on full load or not explain in detail. thanks
Why mostly the HV side of transformer has Delta?
how to calculate distance between busbar supporters for LT panel, what are the factors influencing in this design
Define bibo stability.
Define pole pitch?
how generator load test is conducted?what are the steps?
what r PID controllers?why they r used?what is there purpose?plz Explain in detail
how to calculate the power factor when instantaneous voltage and current has harmonics in it ?
As a electrical engineer.. what are the basic norms should follow in transformer oil testing.. 1.What is the Electrode type? 2.How long time you will give for oil testing?
what is booster? and how it is connected in a circuit?
What is current & voltage ? Voltage perform at any load without current or not?