I have 4 DG set with 1500KVA rating. system breakers are
11KV & alternator are 415 Volts. i want to Know what is
max. resistance for body earthing & 415 & 11KV V Neuteal
earthing. my fault current is 14 times for 2 sec.
Answer Posted / h r jadhav
body earthing resistance max limit is prescibed by
electricity rules 1956. in any case touch potential step
optetial shall not be more so the curent passing live body
more than 30 miliamp.in case of 415 volts max earth
resistance shall not be more than 3 ohms. and in case of 11
kv it is to be less than .6 ohn.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
What is the feedback in the control system?
what is gridrotor resistance starter
In 90 kva alternator that produce the output voltage is 115(p-n),200(p-p) at 1500 rpms means what ampere it produced ?
What are m circles?
How good are you in resolving the commercial issues to Employer's advantage?
What is the role of Dedicated earthing in UPS System?
WHAT IS DEGREE OF COMPOUNDING IN D.C MACHINE MEANS? HOW TO READ THE OPERATING CHART FOR ANY ELECTRICAL MACHINES?
1. what is usage for power factor in industries?? 2.why we need to monitor power factor??
What is an automatic controller?
What are the main parts of central chiller plant? Explain the function of each stage.
WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?
When calculating the speed of a rotor required for a particular frequency of synchronous generator we use the equation 60f/p Is this p is the number of pole pairs of rotor & do we consider the number of pole pairs in the stator is 1?
electromechanical relay type identification example : type=tjmh t-stants for j- m- h-
what is the synchronous timer ? and it applications.
Why CBCT rating is 50/1A