what is reset windup in integral control?
Answer Posted / www.islamqa.com
"Reset windup" is a controller problem that occure when
there's an upnormal load disturbance, which make Pv away
from Sp although the controller is 100% o/p!!
in this case the controller will continue to integrate the
error signal upward, so we can say we have "reset wind
up ", and the valve (or final control element) is taking
its extreme position - up to this we have no problem.
# The problem starts when the unusual disturbance is away
and the controller extreme o/p will have an effect on the
Pv which now on it's way to equal Sp.
The problem now is that the controller seems like to
saturate at 100% due to time spent "winding up", Now we may
have Pv=Sp and the controller remain saturated at 100% o/p,
it will take a long time before the controller start to
downward its o/p value.
# Modern PID has "anti reset wind up" feature, which may
contain an algorithm to turn off the integral term in case
of error is exceed a specific value, or any other algorithm
to stop integral accumulation in case of winding up.
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
ahmedsabry.online@gmail.com
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 13 Yes | 1 No |
Post New Answer View All Answers
I want to measure and control level in tank of size 10*5 filled with gasoline, so plz give me the solution with clear details. how to select transmitter and sensors.
what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail
how to work static pressure sensore how to work dpt
What is three element drum level control system why its better than single element?
Define the difference between a stable versus an unstable controlled system and some of the tools you might use to be able to detect when this is happening and assumptions used for control system application design that could contribute to instability
How RAL(Rotary air lock)works in cement industry?
how many pulses are required by a ac induction servo motor of 4 poles with 50 Hz frequency to rotate by 1 degree?
Explain types of valves?
why we take %i0.0 as input for twido plc
tell me the field & lab calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter, temperature transmitter, temperature indicator, flow indicator, level indicator, control valve, thermocouple, pressure indicator (digital & analogue),
I need to know steps to Calibration Valve Guard......
Why the ammonia and Nitric Acid level indicators is with millimeter ? and What is the conversion form millimeters that level indicator indicate to weight ?
what is temperature compensation?
kindly sent some demo question and answer
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?