Answer Posted / www.islamqa.com
#"Cv" for valve is known as: valve sizing coefficient or
valve flow coefficient
#It refers to " how many gallons per minute can pass
through a fully open valve under diffrential pressure of 1
PSI "
#Cv is a unitless value and by getting it's value we can
get the valve size in inch from tables.
#Cv is got from calculations using s/w provided by
manufacturer as we have many parameters affect its value,
and Cv value is critical as it affects valve size which
leads us - if wrong - to oversized valve or undersized
valve, which harm the process.
#Cv - as mentioned - is got from calculations using s/w,
but it has a basic formula for gas service and liquid
service.
#For liquid service:
Q = Cv (DP/ROH)^.5, ROH IS SPECIFIC GRAVITY
#For gas service:
Q = 963 Cv (DP(P1+P2)/ROH*T)^.5, T is gas temperature in
Rankin
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
ahmedsabry.online@gmail.com
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
what is span value and zero ? and how set ?
Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?
How we calculate orifice plat size???
HOW TO CALCULATE ACCURACY OF AN INSTRUMENT. WHICH IS COMPITABLE FOR USE.
We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.
How a conductivity sensor & analyzer work at boiler, whats the principle & science is beyond this,How conductivity sensor sence & convert signal & move toward analyzer & analyzer show reading in percent? also what is temperature compensate option in conductivity analyzer
How process line mpm calculation is done?
Q- Control problem are mainly classified in _____ types. a-)4 b-)3 c-)6 d-)nono of these Few of them i know is 1- regulator type problem (eg- Air conditioner) 2- tracking problem (eg missile trcking problem) 3- sybernatics 4- optimal control problem
What care will you take in the installation of control valves,SCADA,DCS and FOC in Oil and Gas Project?
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.
What is first echo & echo window in radar type level transmitter?
-/5A. What is the meaning and limitations of this in energy meter constant. It is a 3 phase LT Energy Meter. If this Energy Meter is connected through a CT of ratio 200/5 Amps, then what is the multiplying constant and how its will be calculated.
Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?
Explain bernoulli’s theorem.
How to measure the dust in chimney(spm)?