how to install Differential pressure transmitter in gas
line.i need transmitter down side.
Answer Posted / www.islamqa.com
Bharathi is right, we have to use "condensation pot"
# Actually the gas is "self venting" and the instrument
mounting should be above the pipeline in order to avoid
vapor condensation which cuase fault reading.
# For liquid service the instrument mounting should be
below the pipeline as the liquid is "self draining".
# If we want to mount the instrument below the pipeline in
gas service we should use "condensation pot" and the
operator should drain it regularly to avoid fault reading.
# In steam service we use the condensation pot also and it
should be fully filled with water and its mounting should
be in the same pipeline level and the instrument itself
will be below the pipeline, this link indicte the situation:
http://www.eng-tips.com/viewthread.cfm?qid=166893&page=97
the aim of water filling is to provide a solid motion
transfer in order to have a good accuracy.
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 14 Yes | 1 No |
Post New Answer View All Answers
Why not come out analog output in ABB EL3020 when display show correct value
in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose
What pressure results for a flow transmitter of range 0- 180t/h in the dcs and 0-301mbar in the field using square root extraction. Kindly also suggest formulae for the percentages 0,25,50,75,100?
Draw a wheatstone bridge circuit showing supply, meter and 3 wire RTD connection
the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)
why we are using digital signals for I/O & how to measure this signals is getting or not ?
Explain the working of an electronic level troll.
which type inter lock use in petrochemical refinery,and oil & gas?
Which type of pressure can be measured by primary elements?
what is diffrance between FF & SMART, explain with difination
how to work MIL contol valve posistioner ?
What is instrumentation instrumentation engineering?
how u calibrate sox nox co2 co in cemps?what is opacity n HPm?tell the standard parameters of cems?
How we connect a instrument with ground, Give brief explanation with help of diagram?