what are the specifications for Dc cables of higher rating

Answer Posted / loboreliance2003

The DC voltage rating for high voltage insulation does not
take into account RF coupling of high voltage AC Signals
through the insulation to grounded objects. It is found
that high voltage wire insulation must be de-rated by
approx. a factor of four for the high voltage frequency
levels used. For instance, to run a 10KV triangle wave at
1KHZ requires insulation on the test cables with a DC
rating of at least 40KV.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to calculate the surge level of surge suppressors related to the SF6 cicuit breakers?

1557


why we use two slope(differential & restraining) in differential relay.but in busbar protection differential we are using only one slope?please explain

1735


Is Transol transformer oil comparable to nynas nytro libra?

2632


HOW TO CALCULATE THE HEAT AND LOAD OF LT-SUBSTATION WHICH CONTAINS 2*1MVA TRANSFORMERS,LT-SWITCH BOARD,MLDB,ACB,BUSBAR,ETC,......?

1628


What should be the length of transmission line so that we can see/obtain the full sine wave of voltage??

1418






For refrigerators the motor current is raised beyond its rating on both conditions when the voltage of the system is more(say 270v) than the rated voltage(220v) as well as when the voltage of system is less(say 160v) than normal voltageof 220v, why explain?

1528


1)what is the function of a frequency inverter? 2)If a few frequency inverter are connected onto a device network,what are the two setting that will ensure the frequency inverter work properly on the network. 3)whats is the name of the input sensor for weigher? 4)How to confirm that the load cellis faulty? 5)Describe briefly the steps to validate that the weigher is working properly? 6)Describe the procedure to validate the flowmeter accuracy? 7)Describe briefly the steps to validate that the tempreture sensor/transformer is working properly. 8)what is the adjustment that need to be done when you are calibrating the temperature transmitter ? 9)what are the safety measures to be taken before disconnecting motor for rewinding. 10)whats is the synchronous speed in rpm of typical 4pole 50hz motor? 11)whats is the formula for kw, ohm's law 12)if a 3phase motor is rated 3kw,415vac,what is it's rated ampere?

1382


for a 500 KVA connected load, I calculated 30% of capactor for power correction. Even after using 225 KVR capactor PF is not improving. What could be reason for low Phase correction factor?

1541


what do you mean by class PS CT and what are technical details needed for calculating it?

1524


what is the operating time for LBB and how does the LBB relay realise whether cb is opened or not?

1499


The ripple frequency in output of fullwave bridge rectifier is a. Half the input b. Twice the input c. Same as input

1815


Why are cables rated for 40 KA for 0.25 Sec fault current rating?

1522


Why does the speed regulating system adopting I controller have no steady-state error? In this single closed-loop speed regulating system, when the input of the I controller Un=0, what is the output voltage of the regulator? What factors do the output voltage depend on?

1424


I don't understand why when we connect high voltage source in DC to electronic motor , we must add capacitor and resistor in parallel ? (I know that we use capacitor because we want to absorb the current that in the first second electronic motor in opposed with current course produce. ) what are the feature of Resistor and in such situation ?

1378


at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)

1472