how u measure dp in dp tx? how u calibrate a dp tx?
Answer Posted / senthil
CALIBRATION OF A DP TRANSMITTER VARIES DEPENDING ON ITS
RANGE ( POSITIVE OR -IVE TO +VE)
FOR EXAMPLE:IF THE RANGE IS 0 TO 10BAR IS THE RANGE-
U HAVE A FIVE WAY MANIFOLD ON THE
TRANSMITTER.THE POSITION SHOULD BE
- VENT VALVE TO BE CLOSED
-LP ISOLATION VALVE IS OPENED AND VENT TO ATM
- CONNECT THE CALIBRATOR(DRUCK OR HYDRAULIC PUMP) ON THE HP
ISOLATION.
SINCE OUR RANGE IS OF POSITIVE VALUE.WE APPLY CORRESPONDING
PRESSURE ON THE HP SIDE..0,2.5,5.0,7.5,10
FINALLY DONT FORGET TO CONFIGURE IT AS SQUARE ROOT USING
HART COMMUNICATOR IF WE USE IT FOR A FLOW MEASUREMENT..
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
What is the purpose of bypass valve across AS valve.
how many maximum enter 2mm Dia solid cylindrical pipe into 8mm Dia hollow cylindrical pipe. give answer with calculation.
ORP sensor working principle?
i want to know the interview format fot gail, instrumentation. pls answer me in habib.sami1003@gmail.com
what is the input of digital counter during the the calibration time?
What materials are used in thermo wells?
selection of the zener barrier for the hazardeous area zone 0
How to convert milliampares into flow??
How to decrease opening & closing time of on/off valve?
what is output of FOUNDATION FIELD BUS transmitter
I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration So is there any causes biside this or any permissives ?
Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?
What is profibus?
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem?