what is the minimum dielectric stregth of transformer oil.
Answer Posted / irfan ahmed farooqui
For a new insulating transformer oil(called virgin oil),
the,
value is 70kv for a good satisfactory level but, where as
oil in use (called in service) has values ranging from 25
kv to 50kv , depending upon various factors like ,running
hours of use, impurities, moisture content, sludge content
etc, but it is advisable to discard old oil, if value does
not improve after dehydration and filteration above 60 KV
in laboratory setup or the oil has not passing a
compatibility/mixibilty test with new transformer oil at
different ratio to come to at par in usable ranges as per
standards, on the other hand the exact values and correct
figures for Virgin oil are available in IEC-60296 AND for
oil in service there is a complete guide and specification
available as IEC-60247 where all the nesseccary
informations are available,including the test methods and
apparatus required.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
Mention the disadvantages of low power factor?
how to calculate percentage impedence at 75 deg C at normal tap
What is Servo Ventilated Motor?
what is the circutor?why we use it ?
What is the Minimum winding resistance of motors ( small & big)? referance range
how can i improve the power factor in domestic (230v)
How we can calculate the Amps for the cable Ex:- For 1sqmm wire how many amps we can draw (calculation)
What are different types of control systems?
how to calculate sizing of NGTR (Transformer rating,Loading resistor value and Current rating of resistor) and what is the X/R ratio. Details : 11kV,Capacitance 1.73532 micro farads,40kA for 1sec.
what is thermal resistance of PVC Cable.
what is the pre charge circuit,what will be work which function it will be use plz tell me
How to calculate the heat load for a electrical room
What is the rotor frequency of 10 Hp 1440 RPM 50HZ 415V ?
state the working principle of incondenscent tube?
Why in power plant projects we see DOL starting method used for motors upto 160 kW instead of star delta method