if in a level tx height is given, how u calculate the ranges
of the tx?

Answer Posted / s. kanniyappan

In case of Dry Leg
Span = (X)(Gl)
Hw at minimum level = (Z)(Gs)+(Y)(Gl)
Hw at maximum level = (Z)(Gs)+(X+Y)(Gl)

In case of Wet Leg
Span = (X)(Gl)
Hw at minimum level = (Y)(Gl)-(d)(Gs)
Hw at maximum level = (X+Y)(Gl)-(d)(Gs)

Gl=Specific gravity of tank liquid
Gs=Specific gravity of seal liquid
Hw=Equivalent head of Water
X=Max level
Y=Min level
Z=Distance b/w Datum and Transmitter.

Is This Answer Correct ?    0 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How is PH sensor works ?

1575


please tel me the calibration of pneumatic controler.

1736


We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1146


how many types of preheaters are in cement industry & what r they can any body explain?

1323


State some of balance principle’ advantages?

659






1.what is the effect of vapour presuure in orifice plate flow measurement 2.which is more effective 2 pressure sensors or one single differential pressure sensor in orifice plate measurement 3.how to design a v/i converter and i/v converter 4.how many type of thermocouple are there 5.how many leads are there in thermocouple measurement 6.how pressure sensors are connected in level measurement in differential pressure method 7.what is the output of capacitive pressure sensor (ac or dc),how its o/p is signal charactarized 8.what is the physical meaning of discharge coeeficient,why it is calculated,orifice plate what is its value,why it is less than 1,Q at upstream is equal to or not equal to Q at downstream of orifice plate why?what is vena contracta in orifice plate 9.why rotameter is called variable area flowmeter,it can measure flow even if area is not varying,why it is made tapered 10.design a 10 bit counter ,which counter you will prefer 11.how to remove self heating error in RTD 12.which is more sensitive pt100 or pt50 13.why thermocouple are connected in parallel 14.what is lead contact error in RTD,how to avoid 15.what is P,PI,PID,PD controller,why there is no ID controller 16.what is override,split range,sequential,ratio,feedforward,cascade controller 17.why we moved from SR to JK and then JK to master slave JK flipflop,give correct reason 18.how to measure level of a closed container which contains vapour and liquid,remember no vapour gas should be leaked,so ultrasonic and capacitive is not an option,design another method 19.how to design horse race counter including sensors and signal conditioning element 20.what is bevelling

1963


What is the difference between working pressure and calibration pressure of a control valve

2587


A valve in series with an orifice plate (DP transmitter), is aligned for constant pressure in the pipeline, if there is an error dx, How to align it in process.

877


How to Calibrate Level Troll in field

772


Why upper weighing limit of electronics balance is 90% of the total weighing capacity?

1672


What is offset in a control system.

7969


Do you have reference list?

1433


What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?

991


plz you help about Que paper of mahagenco previous your,any model paper relad to it{maharastra power genration}

1896


in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.

2297