Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

formula for incomer breaker size calculation of powerfactor
correction unit

Answer Posted / matt

Given a system power factor of 0.9, PFC unit of 50kvar we can work out the following

50/0.9 = 56 A real current

56^2 * 50^2 = 75 A apparent current

Cable capacity - 75 * 1.35 = 100 A

Factor of 1.35 used for over rated capacitors as per
industry standards.

Breaker shall be rated at less than the cable capacity but greater than 75A. Increase cable size to suit breaker breaker sizing if required.

Is This Answer Correct ?    6 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is different bewteen low or high impedance busbar protection scheme

4176


why ten delta testing is carried out on power transformer

1859


What is the difference between the transmission line and distribution line?

1204


What are the causes for the failures of sandwich type (Al) busducts?

1915


What should be current in the Primary and secondary side of 1000KVA (11KV Supply)Transformer.?

1113


what is lumped and distributed elements?

1999


How they LT panel busbar size choose

1734


why constant voltage transformer should be start without load? and if started then what will happen?

2085


how can we find thae value of capacitor for single phase motor. what is difference between starting capacitor and running capacitor.

2428


Define coil span?

1129


How would you relate your key competencies to this position?

2265


What is mean by hot and cold loop testing?

1151


why it is not advisable to run low rating (19KVA) DG sets in parallel for long durations even though they are provided with droop ckts (QDC)

1956


HOW DOES THE ELECTRONIC ENERGY METER WORKS?

2212


where does 22kv line starts

3147