what is the formula to find battery back up of ups?
Answer Posted / bala_vlsi
Fomula
Watt/d.c voltage )x 1 / (p.f )x (1/ Efficiency) x Required
Hrs
Example
Data
500 W = load
12 V = d.c vOLTAGE
0.9 = P.F (ASSUMED )
0.8 = mAINTAINANCE fACTOR(ASSUMED )
500 / 12 X (1 / 0.9 ) X (1 / 0.8 )X 2= 115 AH Battery is
need to priovide 2 Hrs back up supply
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
What is a parabolic signal?
Give details of your interested designation, the post you are interested to serve the company better and explain why you think you can serve the company better in such position if employed?
why do we use spark detector inside the slip ring brush compartment 0ona slip ring induction motor?
can any tell me why slope 40% and 80% is calculated in differential protection?
how is working bearing heater?
What is acsr cable and where we use it?
What is difference between start imitation and start interlock for 3 phase motor protection ?
Advantage of LT panel vs HT panel
What is ferro-resonance in electrical system? Why it occurs and what are measures to prevent it?
Why ground terminal is used in pot meter 10k ohms
what is the meaning of 5% droop or 7% droop in AVR?
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
HOW TO CALCULATE S/C,O/C,E/F OF ACB.
How many types of faults are there in 3 phase power system?
why ct ,cvt should be stored in a vertical position?