Hi friends, from Aug 4th onwards iam getting spikes for
analog inputs in our DCS for a period of 800ms. I throughly
checked every thing, finally i found that the DI, DO's from
MCC panels shields are terminated in the Signal Earth where
Analog Input signals shields are terminated. Is there any
problem with this type of termination?. i checked the
induction voltage from MCC and getting around 25VAC, please
suggest me in this concern. Our plant is 8months old only.
DCS is Siemens Make Simatic PCS7, and the transmitters are
Yokogawa make.
Answer Posted / sankarithi
Hi Friends only problem is due to earth pit. I throughly
checked every thing, finally i found that the Earth pit
totally became dry. I serviced the pit,Now there is no
spikes.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
what is a good line as ic engineer as maintenance ,oc, project, calibration ,validation engineer?
how do u calibrate the vacuum transmitter if it shows more reading
what is the difference between scaler and vector drive
what is cems analyzer explain with principle and drawing ?
What is modbus?
Introduce yourself which is not present in your biodata?
What do you know about gail?
how to relay switch sense the fault?
How to calibrate Toxic gas detector?
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
Programmable Logic control.
How to calibration a control valve?
what is orfics working in main steam line. is it increase pressure, velocity of steam flow and dicrease steam flow rate. or any other
Which products are available in the Mass Systemswitch and System Manager AC range?
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?