Hi friends, from Aug 4th onwards iam getting spikes for
analog inputs in our DCS for a period of 800ms. I throughly
checked every thing, finally i found that the DI, DO's from
MCC panels shields are terminated in the Signal Earth where
Analog Input signals shields are terminated. Is there any
problem with this type of termination?. i checked the
induction voltage from MCC and getting around 25VAC, please
suggest me in this concern. Our plant is 8months old only.
DCS is Siemens Make Simatic PCS7, and the transmitters are
Yokogawa make.
Answer Posted / sankarithi
Hi Friends only problem is due to earth pit. I throughly
checked every thing, finally i found that the Earth pit
totally became dry. I serviced the pit,Now there is no
spikes.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
What happen if I install my pressure transmitter below the elevation of pipe in natural gas service?
How to regulate the flow of Air in 4" line, with max flow of 330 nm3/hr and Pressure of 0.5 bar? please suggest the type of instrument required.
how does we calibrate a square root flow transmitter ,give an example and explain it step by step like range calculation , calibration hook up series connection , zero check , and how to apply pressure , and if not geting proportional output then what should we do ?
Coal mill Instruments Equipments for cement plant And process diagram ?
a flow transmitter [range-0-400mbar] connected in process line. please explain me how to calibrate the flow transmitter , & how to do static error
in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?
what is 24vdc live and dry supply
hii my name is sujith...i am preparing for HPVL GET 2010... so ,,,pls help me by send any previous questions or material to my site.....(Msujith_12@in.com) thank q
what is the calibration procedure for magnetic flow meter @ onsite
How to calculate P,I&D value in PID controller ?
please tel me the calibration of pneumatic controler.
what are the documents(Construction point of view for a process plant) submitted by contactor initially entering in to new site for client?
IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?
How to check vortex flow meter is in good condition while we do not having calibration setup?