Answer Posted / guest
1.Fix the transmitter on the process line and connect the
power supply.
2.Connect the impulse line to the transmitter.
3.Ensure level transmitter HP and LP main isolation valve
is closed.
4.Open the HP and LP valve and close the equiliser valve to
the transmitter.
5.Close the vent plug to the transmitter.
6.fill the water (condensate pot via) on LP side of the
transmittre impulse line.
7.Ensure transmitter display showing is zero.
8.If not showing zero,release the air lock (vent plug via).
9.Open the HP and LP main isolation valve.
10.Ensure the level transmitter working is normal.
| Is This Answer Correct ? | 10 Yes | 3 No |
Post New Answer View All Answers
How we calculate orifice plat size???
send me last 5 years questions asked in rrb chennai, for section engineer
Q1: Consider part of a control loop, which excludes the transmitter, consisting of a process, a controller and a control valve which may be represented by two dead times of 0.5 min each and three exponential lags of 0.8 min., 1.0 min. and 1.5 min. respectively. We wish to express this system as an overall first order plus dead time (FOPLD) model ie gain, time constant and process dead time. (We will see later that this is often done, to simplify controller tuning). For this exercise, gain is considered to be 1.0. (A) If the transmitter is a flow transmitter whose behaviour can be described by a dead time of 0.2 min. and an exponential lag of 0.5 min. in terms of the overall dead time and overall first order lag how can the system behaviour be approximated ? Overall dead time = Overall time constant = (B) If the transmitter is a temperature transmitter with a temperature sensor in a protecting well whose behaviour can be described by a dead time of 0.7 min. and an exponential lag of 15 min. how can the overall system behaviour be approximated now? Overall dead time = Overall time constant =
where proximity sensor installed on tank in loading arm application
what are the selections available in configuring a burnout protection of a controller? thanks
Definition of reverse and acting controllers:
1.what is the effect of vapour presuure in orifice plate flow measurement 2.which is more effective 2 pressure sensors or one single differential pressure sensor in orifice plate measurement 3.how to design a v/i converter and i/v converter 4.how many type of thermocouple are there 5.how many leads are there in thermocouple measurement 6.how pressure sensors are connected in level measurement in differential pressure method 7.what is the output of capacitive pressure sensor (ac or dc),how its o/p is signal charactarized 8.what is the physical meaning of discharge coeeficient,why it is calculated,orifice plate what is its value,why it is less than 1,Q at upstream is equal to or not equal to Q at downstream of orifice plate why?what is vena contracta in orifice plate 9.why rotameter is called variable area flowmeter,it can measure flow even if area is not varying,why it is made tapered 10.design a 10 bit counter ,which counter you will prefer 11.how to remove self heating error in RTD 12.which is more sensitive pt100 or pt50 13.why thermocouple are connected in parallel 14.what is lead contact error in RTD,how to avoid 15.what is P,PI,PID,PD controller,why there is no ID controller 16.what is override,split range,sequential,ratio,feedforward,cascade controller 17.why we moved from SR to JK and then JK to master slave JK flipflop,give correct reason 18.how to measure level of a closed container which contains vapour and liquid,remember no vapour gas should be leaked,so ultrasonic and capacitive is not an option,design another method 19.how to design horse race counter including sensors and signal conditioning element 20.what is bevelling
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
selection criteria of control valve? and selection criteria of actuator explain in brief?
Explain signal isolator
hi friends,im an instrumentation and contol engg student,can u hlp me of suggsting barc written question paper,my id is roysuvaranjan@gmail.com, cel no.9563591747
If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
what is the different between deflection type measurement and null type measurement in RTD?
hiii.... can any one provide me previous years question paper of hindustan petroleum for instrumentation engineering???