how to choose the cable rating for load (KW)? EXAMPLE.50KW load
Answer Posted / m.saad
Calclate the load Current
I = p/((root3)*V*P.F )
where I line current, v line voltage
then go to cable tabe
and check the Drateing factors.such as
if this cable underground,free,soil,depth of laying,
ambient temperture, armoed or unarmoed etc.
then calcute the voltage drop
if more than 4%
you should to select the next bigger cross section at table.
by experince for copper PVC cables
1mm take 2.5 AMP
| Is This Answer Correct ? | 32 Yes | 13 No |
Post New Answer View All Answers
i have interview in Pepsi company what type of question will ask please send the question and answeer
difference between servo motor and synchronous motor
While testing a ZCT what parameters have to check or measure?
Has someone here done a sizing for a generator (3 phase), its for a pumping station. If you have an example for standby/duty and both running (I) star delta (ii) Soft Starter.
what is the terminal voltage of dc series generator running at rated speed at no load?
in ACB breaker requireding 3200Amps. buscoupler getting OFF mode and again it reset and getting normal position give me a required answer?
Where servomechanism is used?
how a flip flop can be used as a latch?
What is capacitance?
What is signal flow graph?
to vary valtage from 0 - max a variac is necessary . so how to design for high power applications nearly about 200KW power
what is efficient motors and how it is different from normal induction motors
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.
Show Details FROM:Muhammed Ikram TO:qa@allinterview.com Message flagged Saturday, June 4, 2011 10:07 PMMessage bodyHello all, i want to ask a question to all of you that what is VMM (voltage monitoring module )? how it work,s? i heard somewhere that it compare 1 phase voltage to other phase voltage. but there is also some setting on it. how to set it,s setting. please tell me briefly. Thank,s and Regard,s. Muhammed Ikram.
how we design a pannel to start 10HP motor with the help of star delta starter?