what is the working of loss of excitation relay (40G)? how it
is work?
Answer Posted / k.prakashchandra
LOE relay acts ,as its name indicates, when excitation fais
either due to field breaker(FB) opening or some other
cause.When there is no excitation the gen will run as synch-
motor or induction generator if the prime mover still
running. In both the cases current will be drawn from the
system ,hence power flow is reversed .Then the relay acts
to actuate the master trip.Earlier this relay acted only
when FB opened, closing a switch in the opened position .
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
any one please tell taht what type questions will be asked in BHEL interview, i am having interview on 24th Dec, please send this to mail pradeepsistam@yahoo.co.in
What is the limitation of kirchoffs law?
Wt is the function of reactive power? How it generates & consume though resultant is zero?
Can anybody tell abt concrete encased earthing or grounding?
what is the star delta connetion and how can do it a three phase motor with control witing with picture
hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.
How to Calculate The sag of OPGW in Transmission Line???
How convergengr of nr method is not dependent on selection of slack bus and how gauss siedel method depends?
Why use the vcb at high transmission system ? Why can’t use acb?
why the NGR (neutral grounding resistor) always OFF during DG off?
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
What is mean by hot and cold loop testing? What is the difference between them?
Show the schematic arrangement of diesel power station layout and give its principle of operation.
sir i want previous entrance exam papers for written test
What is the formuala to calculate the rating of motor protection circuit breaker