What is the advantage of Neutral graunding transformer
insted of Neutral graunding Resistance in generating
station explain briefly.

Answer Posted / amit khamesra

NGR and NGT serves the same purpose of limting the earth
fault current to the rated values which basically depends
upon the core damage curve of generator. Differece is NGT
gives earth fault protection of 100 % winding whereas NGR
protects only 95% of the generator winding. Potential
difference of the 5% winding (towards neutral) with respect
to neutral is very less so the earth fault in that region
of the winding is not sensed. This is avoided in NGT using
sensing of 3rd harmonic under voltage based principle in
secondary of the NGT.

Is This Answer Correct ?    3 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is stper motor

1991


If we want to change a contactor of faulty one what are the conditions want to fullfil

1545


HOW TO CALCULATE ELECTRICAL, MECHANICAL,& OVERALL EFICIENCY OF GAS ENGINE POWER PLANT

1540


What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?

1724


what is advertised hop count

1281






what r PID controllers?why they r used?what is there purpose?plz Explain in detail

1626


Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?

1242


What is difference between safe PLC and normal PLC

1000


explain Density

654


internally connection of photvoltic module

1463


how to calculate units consumption for a 12 hp motor /hr.

1039


list the type of vfd? wich is sutable for heating kiln?

1609


difference between the applicability of nortons and thevenin theorem

1559


what is the basic construction diffrance between servo motor ans sqiralcage induction motor

2018


at work we have a 3 phase motor but on testing one phase isnt getting a reading. it runs 24 hours a day all week. stops and starts well no noise or heating. the phase isnt down to earth.is it just a bad meter reading or not? phases one and three came up with a resistance reading of 0.4 but phase 2 couldnt get anything shows up as open circuit.

1186