hi i want sov loop cheak from consol to field the operater
given status to sov still no change, but MR room to sov ok
so whats a problem and alreasy cheak all conection ok ?
Answer Posted / jai
1,Confirm the function of SOV,if its OK,
2.Measure the vlotage across the SOV..it should be 24 VOlt.
3.If it is not matching with supply voltage measure the
coil resisitence of SOV...resistence should equal to
manufacturere resistence value
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
I have completed B.E. Instrumentation & control in 2009. i have 3 year industrial job experience in chemical plant.now, I want to join M.E. in external. so, Plese say easiet way and good institute name.
I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.
What is first echo & echo window in radar type level transmitter?
Explain bernoulli’s theorem. State its application.
how to control pid
what is exact time to study dcs and plc cources
Where is wet leg is used?
what is sil (safety integrity level
can you provide me full detail about instrumentation in ONGC??
how do calibrate the valves.. with clear manual
What is intrinsically safe system?
Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?
what is the procedure of O2 sensor(ABB) calibration?
State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.
How earthing can be checked????