hi can you give any body fault level calculation, generator
fault level calculation,transformer fault level calculation
for system fault level with equation? i have 3.3kv
generation voltage three gas gen sets, one is 1.9MW,2nd is
2.5MW,& 3rd is 3.8MW & i have 11 kv generation voltage one
gas gen sets is 3.8MW, we are step up to 22kv by transformer
Answer Posted / dhiren
Hello Rajeshbhai,
You have not mensioned the capacity & impedance of the
transformer
for example if we have
A 5MVA, 11/22KV transformer with a 5% impedance.
Maximum fault MVA will be
5MVA/0.05 = 100MVA
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
If we need4× 50mm sq cable but it's not available so we can pull 4×25mm sq 2cables
How could a garment factory benefit from renewable energy
how to select overload-relay for perticular motor 1.for D.O.L. starter 2. for Star-delta starter ????
what are the necessary basic electrical topics to learn for mechanical engineer to deal practical problems.
what happen if the parallel generator phase angle shift by 1 degree in manual mode
What is meant by a stray loss of a induction motor??? What is the equation to find it
What is vacuum circuit breaker.define with cause and where be use it device?
how to calculate the capacitor to maintain power factor?
How to calculate LT XLPE CABLE for 11 kv / 433 v , 1000 kva oil type transformer system?
what is the range of maximum DOL and SDS can be use for pump and fan application
i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh
what is is the potential diffrence between two phase ?
PLZ EXPLAIN THE INTERLOCKING AND CONTROLLING OF CONTACTORS????HOW CAN I DO THAT?
what is electrical machines
how oil in the MOCB was reduced compared with OCB? what are the features of the MOCB?