my 10 hp submersible pump is tripping when connected
through ELCB.I have checked the megger value of the coil's
with body.It was found to be 0.2mega ohm.that is leakage is
there.But when connected to mccb it is not tripping.no
leakage current in the motor.Is it safe to connect to mccb?
what are the problem's will arise if future?also tell me in
ELCB no neutral is connected to motor.than how ELCB was
working?
Answer Posted / virendra joshi
There may be a minor leakage in , also please check the
mAmp of the ElCB if it is 100ma then there is a possible
chance of tripping on minor leakage.. i suggest you to try
with 300ma ELCB even if get tips then you have to check the
motor winding & connecting cable thoroly.
| Is This Answer Correct ? | 9 Yes | 1 No |
Post New Answer View All Answers
Explain Even and Odd signals?
Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m
What is the resonant peak?
what is PID control in VFD drives?
What is marx circuit?
What is difference between SMC supportg and Glass Fibre Reinforced Plastic Support.
Briefly describe means used by electricity suppliers to influence the flow of active and reactive power in power networks (one for each type)?
Why mostly the HV side of transformer has Delta?
what is the principle of the single phase energy meter? and,what is the advantages and disadvantages of single phase energy meter?
what is the carona effects meaning in HT line transmmission system
Difference between on line capacitor and Station type capacitor
Why does curving the pole faces in a dc machine contributes to a smoother dc output voltage from it?
what is v/f control in VFD?
Can u Explain about the electronic trivector meter and the use of data converters in them?
how many safety really of DG sets.