Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is the difference between earthed & unearthed system?

Answer Posted / meenakshi

By Earthed system, we mean a three phase system whose star
point is grounded directly. In this case, in the event of
the earth fault, the voltage in the faulty phase will
become zero. The voltage between the healthy phases and the
ground will be the same, 11kV/1.732 or 6.6/1.732.

However, in case of an earth fault in an ungrounded system,
the voltage between the healthy phases and the ground will
be equal to the phase to phase voltage. i.e. 11kV or 6.6 kV.

Is This Answer Correct ?    6 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is meant by poly phase induction motor ? how its operating by single phase or three phase?

2101


What is float cum boost charging system?

1998


how can calculation ate Amps for cabel. Ex-for 1sqmm wire hou many amps we can draw

2386


circuit diagram of trip circuit supervision relay

1994


What are the specifications for getting approval of Substation?

1870


Electromagnetic torque developed by the motor is compared to shaft torque. A less B same C depends on motor design D more

1989


300m long and 30kw inductive loade 3phase supply how many size cable required

1376


direction of tarbine& genrator

2037


Y phase plates are used in transmission line??? what is there need???

2858


aternator every parts and its working

1577


What is the difference between isolators and electrical circuit breakers?

1092


How to calculate cable size by using load.?? Any formula...

1310


what is the problem when i want to close a circuit breaker by local position it closes well.but when i close it in remote position it trips

1547


what is relay what is protection & contact multiplying relays where it is used function in brief

1112


We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2094